Viessmann Vitotwin 300-W Installation And Service Instructions For Contractors page 128

Micro chp boiler based on stirling engine natural gas version
Hide thumbs Also See for Vitotwin 300-W:
Table of Contents

Advertisement

Troubleshooting
Fault messages
Fault mes-
Cause
sage
"270: Exc
Excessive temperature dif-
temp diff h'
ferential between the heating
exch"
water flow and return.
"274: Zero
Flow rate too low after filling.
flow protec-
tion"
"275: Zero
Flow rate too low after vent-
flow aft dea-
ing.
er"
"276: Zero
Inadequate flow rate cap-
flow"
tured in heating mode.
"278: Max
Max flow temperature in-
temp rise"
crease exceeded.
"280: Inner
Generator base excess tem-
iron over-
perature. Thermostat has re-
temp"
sponded.
"281: Dyn
Dynamic absorber overtravel
absorber
switch actuated.
tripped"
128
(cont.)
Remedy
Check the system pressure.
Vent the heating system.
Check whether there is any
throughput (code 8366 in di-
agnostics heat generation)
Check function of the circula-
tion pump.
Check function of 3-way
diverter valve.
Check temperature sensors
and flow sensor.
Check connecting cables be-
tween Stirling engine and
control unit (cables to plug
X205).
Check temperature at bottom
of Stirling engine: max.
100 °C.
Check whether there is a
min. flow rate of 240 l/h (code
8366 in diagnostics heat gen-
eration).
Notify Viessmann Technical
Service.
Check plug-in connection
X205, connecting cables and
plugs to overtravel switches
at the bottom of the Stirling
engine (see page 152).
Check spring length; adjust if
necessary (see page 77).
Notify Viessmann Technical
Service if no fault can be dis-
covered or if unusual noises
can be heard.
Re-
set-
ting
AR
UR
UR
AR
AR
AR
SR