Specifications Of Electrical Parts - Toshiba RAV-GM1601AT8P-E Service Manual

Outdoor unit
Hide thumbs Also See for RAV-GM1601AT8P-E:
Table of Contents

Advertisement

5. SPECIFICATIONS OF ELECTRICAL PARTS

Outdoor Unit
No.
Parts name
1
Compressor
2
Outdoor fan motor
3
High pressure switch
4
PMV-Coil
5
Reactor
6
P.C.board for control and 1 fan motor drive (Upper)
7
P.C.board for compressor drive
nd
8
P.C.board for 2
fan motor drive (Lower)
9
Outdoor temp. sensor (TO sensor)
10
Discharge temp. sensor (TD sensor)
11
Suction temp. sensor (TS sensor)
Heat exchanger sensor (TE sensor)
12
13
Heat exchanger temp. sensor (TL sensor)
14
Fuse (Mounted on P.C.board, MCC-1626)
15
Fuse (Mounted on P.C.board, MCC-1626)
16
Fuse (Mounted on P.C.board, MCC-1626)
Fuse (Mounted on P.C.board, MCC-1627)
17
18
Fuse (Mounted on P.C.board, MCC-1627)
19
Fuse (Mounted on P.C.board, MCC-1603)
20
PTC Thermistor
st
50T(P) 063HF GF_001 C4
- 28 -
Type
RX380A2T-20M
4P, 3750W
ICF-280-A100-1
Output 100W
ON : 3.5MPa, OFF : 4.5MPa
ACB-4UB166W
CAM-MD12TCTH-8
DC12V
CH-86-2Z-T
5.46 - 6.14mH, 18.5A
MCC-1626
MCC-1627
MCC-1603
10 kΩ at 25°C
50 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
50T 100H
T10A, 250V
SLT6.3A
T6.3A, 250V
SCT 3.15A
3.15A, 250V
T6.3A, 250V
GAC1 31.5A
31.5A, 500V
SCT 3.15A
3.15A, 250V
MZ32-101RMARD01E
100Ω, 500V
Specifications
Q'ty
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
2
1
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-gm1601at8jp-eRav-gm1601at8p-tr

Table of Contents