5. SPECIFICATIONS OF ELECTRICAL PARTS
No.
Parts name
1
Compressor
2
Fan motor
3
4-way valve coil
4
PMV coil
5
High-pressure SW
6
Reactor
7
P.C. board
8
Fuse (Mounted on P.C. board)
9
Fuse
10
Fuse (Mounted on P.C. board)
11
Outdoor temp. sensor (TO sensor)
12
Heat exchanger temp. sensor (TE sensor)
13
Suction temp. sensor (TS sensor)
14
Discharge temp. sensor (TD sensor)
15
Heat exchanger temp. sensor (TL sensor)
16
Compressor thermo. (Protection)
Type
DX150A1T-20F
ICF-140-43-4R
STF-H01AZ1724A1
PQ-M01012-000082
ACB-4UB83W
CH-57-Z-T
MCC-1645
-
-
-
-
-
-
-
-
CS-12AL
- 24 -
Specification
3 phase, 4P, 1100 W
Output 43 W
-
-
OFF:4.15MPa
8.88~10mH, 16A
-
AC250 V, 25 A
AC250 V, 6.3 A
AC250 V, 3.15 A
10 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
50 kΩ at 25°C
OFF: 125 ± 4°C, ON: 90 ± 5°C