Toshiba RAV-GM1601AT8P-E Service Manual page 43

Outdoor unit
Hide thumbs Also See for RAV-GM1601AT8P-E:
Table of Contents

Advertisement

n Triple system
<Formula for Calculating Additional Refrigerant Amount>
Do not remove the refrigerant even if the additional refrigerant amount becomes minus result as a result of
calculations by the following formula and operate the air conditioner as it is.
Additional refrigerant amount (kg) = Main piping additional refrigerant amount (kg)
α α α α α
: Additional refrigerant amount per meter of actual main piping length (kg)
γ γ γ γ γ
: Additional refrigerant amount per meter of actual branch piping length (kg)
L
: Actual length of main piping (m)
a, b, c : Actual length of branch piping (m)
Connecting pipe diameter
L
a
Ø9.5
Ø6.4
Indoor unit C
Outdoor unit
1. Be certain to wire the additional refrigerant amount, pipe length (actual length), head and other
specification on the nameplate put on the outdoor unit for recording.
2. Seal the correct amount of additional refrigerant in the system.
+ Branch piping additional refrigerant amount (kg)
α α α α α
= {
× (L – 28)} + {
b
c
Ø6.4
Ø6.4
Indoor unit B
Branch pipe
c
L
Main pipe
CAUTION
γ γ γ γ γ
× (a + b + c – 6)}
Additional refrigerant amount per Meter (kg/m)
α α α α α
0.035
Branch pipe
b
Branch pipe
Distributor
- 43 -
β β β β β
γ γ γ γ γ
0.02
Indoor unit A
∆ h
a
H

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-gm1601at8jp-eRav-gm1601at8p-tr

Table of Contents