procedure
Be sure to put on the gloves at working
time; otherwise an injury may be caused
by a part, etc.
1. Detachment
2. Attachment
Using bundling band on the market, be
sure to fix the power wire and indoor/
outdoor connecting wire along the
crossover pipe so that they do not come to
contact with the compressor, valve at gas
side, pipe at gas side and discharge pipe.

11. DETACHMENTS

Procedure
CAUTION
1) Stop operation of the air conditioner and
then turn off switch of the circuit breaker.
2) Take off the front panel.
(HEX-ST-SCREW Ø4 × 10, 2 pcs.)
∗ After Take off screws, Take off the
front cabinet while pulling it downward.
3) Take off the power wire and indoor/
outdoor connecting wire from the cord
clamp and the terminals.
4) Take off the upper cabinet.
(HEX-ST-SCREW Ø4 × 10, 5 pcs.)
1) Attach the upper cabinet.
(HEX-ST-SCREW Ø4 × 10, 5 pcs.)
2) Connect the power supply wire and the
indoor/outdoor connecting wire to the
terminal and mounting with cord clamp.
CAUTION
3) Attach the front cabinet.
(HEX-ST-SCREW Ø4 × 10, 2 pcs.)
- 87 -
Remarks
Front cabinet
Upper cabinet