No.
Part name
Discharge
1. Detachment
2
port cabinet
1)
2)
3)
4)
5) Take off screws of the discharge
6) Take off screws of the discharge
Side cabinet
1) Carry out work of 1 of 1.
3
2) Take off screws which fix the inverter
3)
4)
5)
6) Take off screws of the side cabinet and
7) Slide the side cabinet upward and then
Procedure
Carry out work of 1 of 1.
Take off screws for the discharge
cabinet and the partition plate.
(ST1T Ø4 × 10, 4 pcs.)
Take off screws for the discharge
cabinet and the bottom plate.
(HEX-ST-SCREW Ø4 × 10, 2 pcs.)
Take off screws of the discharge
cabinet and the motor base.
(ST1T Ø4 × 10, 2 pcs.)
cabinet and the heat exchanger.
(ST2T Ø4 × 10, 1 pcs.)
cabinet and the plate-stay
(HEX-ST-SCREW Ø4 × 10, 2 pcs.)
assembly and the side cabinet.
(ST1T Ø4 × 10, 3 pc.)
Take off screws of the side cabinet and
the valve fixing plate.
(HEX-ST-SCREW Ø4 × 10, 2 pcs.)
Take off screws of the side cabinet and
the pipe panel (Rear).
(HEX-ST-SCREW Ø4 × 10, 2 pcs.)
Take off screws of the side cabinet and
the bottom plate.
(HEX-ST-SCREW Ø4 × 10, 1 pc.)
the heat exchanger.
(HEX-ST-SCREW Ø4 × 10, 3 pcs.) and
(ST1T Ø4 × 14, 2 pcs.)
take off it. (Hook of inverter)
Motor base
Inverter
Inverter
assembly
assembly
Valve
fixing
plate
- 88 -
Remarks
Discharge cabinet
Plate-stay
exchanger
(Fin guard)
Side
Side
cabinet
cabinet
Panel
piping
(Rear)