Toshiba RAV-GM1601AT8P-E Service Manual page 41

Outdoor unit
Hide thumbs Also See for RAV-GM1601AT8P-E:
Table of Contents

Advertisement

n Triple system
Pipe length
(one way)
Refrigerant pipe
specification
Height
difference
Indoor unit C
Outdoor unit
When planning a layout for Units A, B and C, comply with the following:
1. The lengths after branching ("a" and "b", "b" and "c", "a" and "c") should be equal if feasible.
Install Units A, B and C so that the difference of the branching lengths becomes less than 10m if the
lengths cannot be equal due to the branch pipe position.
2. Install Units A, B and C on the same level.
If Units A, B and C cannot be installed on the same level, the difference in level should be limited to 0.5 m
or less.
3. Be certain to install Units A and B and C in the same room.
Units A, B and C cannot be operated independently each other.
Total length (L + a, L +b, L+c)
Branch pipe length (a, b, c)
Maximum difference between indoor units
(|a – b|, |b – c|, |c – d|)
Between indoor units ( ∆ h)
Between indoor unit
and outdoor unit
Number of bent portions
Branch pipe
c
L
Main pipe
CAUTION
When outdoor unit heigher (H)
When outdoor unit lower
Indoor unit B
Branch pipe
b
Distributor
- 41 -
50 m
15 m
10 m
0.5 m
30 m
(H)
30 m
10 m or less
Indoor unit A
∆ h
Branch pipe
a
H