Toshiba RAV-GM1601AT8P-E Service Manual page 75

Outdoor unit
Hide thumbs Also See for RAV-GM1601AT8P-E:
Table of Contents

Advertisement

8-2-5. Diagnostic Procedure for Each Check Code (Outdoor Unit)
Temperature sensor
TA, TC, TCJ, TE, TS, TO sensors
Representative value
Temperature
(°C)
(Minimum value) (Standard value) (Maximum value)
0
32.33
10
19.63
20
12.23
25
9.75
30
7.764
40
5.013
50
3.312
60
2.236
70
1.540
80
1.082
90
0.7740
100
0.5634
40
30
20
10
0
0
200
150
100
50
0
0
∗ As TH sensor (Outdoor unit heat sink temp. sensor) is incorporated in the outdoor control P.C. board, the
resistance value cannot be measured.
Temperature – Resistance value characteristic table
Resistance value (kΩ Ω Ω Ω Ω )
33.80
35.30
20.35
21.09
12.59
12.95
10.00
10.25
7.990
8.218
5.192
5.375
3.451
3.594
2.343
2.454
1.623
1.709
1.146
1.213
0.8237
0.8761
0.6023
0.6434
TA, TC, TCJ, TE, TS, TO sensors
10
20
30
40
Temperature (˚C)
TD, TL sensors
10
20
30
40
Temperature (˚C)
TD, TL sensors
Representative value
Temperature
(°C)
(Minimum value) (Standard value) (Maximum value)
0
150.5
10
92.76
20
58.61
25
47.01
30
37.93
40
25.12
50
17.00
60
11.74
70
8.269
80
5.925
90
4.321
100
3.205
50
60
70
80
50
60
70
80
- 75 -
Resistance value (kΩ Ω Ω Ω Ω )
161.3
172.7
99.05
105.6
62.36
66.26
49.93
52.97
40.22
42.59
26.55
28.03
17.92
18.86
12.34
12.95
8.668
9.074
6.195
6.470
4.507
4.696
3.336
3.468
90
100
20
15
10
5
0
90
100

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-gm1601at8jp-eRav-gm1601at8p-tr

Table of Contents