7.12.7 Insulation of the gas exhaust and air intake

7.12.8 Fitting a horizontal flue system

Installer reference guide
96
I
From a terminal discharging towards another
terminal
J
From an opening in a car port (e.g. door,
window) into a dwelling
K
Vertically from a terminal on the same wall
L
Horizontally from a terminal on the same wall
M
Above an opening, air brick, opening windows,
etc.
N
Horizontally to an opening, air brick, opening
windows, etc.
P
Above roof level (to base terminal)
Q
From an adjacent wall to flue
R
From an adjacent opening window
S
From another roof terminal
-
From an external boundary. Note: If the
terminal is facing a boundary, it is
recommended that an anti-plume kit be fitted.
T
Terminals adjacent to windows or openings on
pitched and flat roofs: The flue should NOT
T1
penetrate this area.
T2
NOTICE
The boiler manufacturer cannot be held responsible for atmospheric conditions
when siting flue terminals.
CAUTION
Once the flue system has been installed and the appliance commissioned, the
installer should observe the plume direction. Particular attention should be drawn to
plume vapour reentering the gas boiler via the air intake. If this occurs, it is highly
possible the flue is fitted with a negative pressure area and therefore a plume
management kit MUST be fitted.
Condensation may occur on the outside of the pipe material when the material
temperature is low and the environment temperature is high with a high humidity.
Use 10 mm damp-proof insulation material when there is a risk of condensation.
The 60/100 mm horizontal flue system may be extended up to a maximum length
as specified in the table indicating the maximum pipe lengths. Calculate the
equivalent length according to the specifications in this manual.
Terminal position
Minimum distance
(mm)
1200
1500
300
1000
600
2000
600
CHYHBH05+08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10