CHYHBH05+08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
INFORMATION
h=Height measured from the floor to the flare nut.
H=Height measured from the floor to the bottom of the casing.
In cases where H≤600 mm, h is always considered to be 600 mm, as specified in
IEC 60335-2-40:2013 A1 2016 Clause GG2.
For intermediate H values (i.e., when H is between 2 H values from the table),
consider the value that corresponds to the lower H value from the table. If
H=950 mm, consider the value that corresponds to "H=900 mm".
For intermediate dm values (i.e., when dm is between 2 dm values from the
table), consider the higher dm value from the table. For 3MXM52 with m
and dm=0.25 kg, consider "dm=0.4 kg".
Following graphics are possible examples about minimum venting opening area for
natural ventilation.
≥VA
min
300 mm
200 mm
VA
100 mm
min
20 mm
0 mm
≥VA
min
300 mm
200 mm
VA
min
100 mm
20 mm
0 mm
WARNING
In case of a different configuration is used, do NOT deviate from requirements
mentioned in "6 Preparation" [
15
4
 36].
Technical data
|
=2 kg
c
Installer reference guide
203