Daikin Altherma R Hybrid Installer's Reference Manual page 187

Hide thumbs Also See for Altherma R Hybrid:
Table of Contents

Advertisement

CHYHBH05+08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
Error code Cause
20, 21, 22,
Sensor fault S2
23, 24
0
Sensor fault after self-
check
1
Temperature too high
2
S1 and S2 interchanged
4
No flame signal
5
Poor flame signal
6
Flame detection fault
8
Incorrect fan speed
29, 30
Gas valve relay fault
13
Possible solution
Check wiring
Replace S2
Replace S1 and/or S2
Air in installation
Pump is NOT running
Insufficient flow in installation
Radiators are closed
Pump setting is too low
Check cable set
Replace S1 and S2
Gas tap is closed
No or incorrect ignition gap
Gas supply pressure is too low or fails
Gas valve or ignition unit is NOT powered
Condensate drain blocked
Check adjustment of gas valve
Replace ignition cable and spark plug cap
Replace ignition unit
Replace boiler controller
Fan catching on casing
Wiring between fan and casing
Check wiring for poor wire contact
Replace fan
Replace boiler controller
Troubleshooting
|
Installer reference guide
187

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents