13.3.9 Symptom: Tank disinfection function is NOT completed correctly (AH-error)

13.3.10 Symptom: Boiler abnormality detection (HJ-11 error)

13.3.11 Symptom: Boiler/hydrobox combination abnormality (UA-52 error)

13.3.12 Symptom: The burner does NOT ignite

CHYHBH05+08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
Possible causes
The disinfection function was
interrupted by domestic hot water
tapping
Large domestic hot water tapping
happened recently before the
programmed start-up of the disinfection
function
The disinfection operation was stopped
manually: with the user interface
displaying the DHW home page and its
user permission level set to
Installer, the
button was pressed
during disinfection operation.
Possible causes
Communication cable problem
Boiler error
Possible causes
Boiler/hydrobox mismatch
Incompatibility of software
Possible causes
Gas tap is closed.
Air in the gas tap.
Gas supply pressure too low.
13
Troubleshooting
|
Corrective action
Program the start-up of the disinfection
function when the coming 4 hours NO
domestic hot water tapping is expected.
When the Domestic hot water >
Type > Reheat or Reheat + sched.
is selected, it is recommended to
program the start-up of the disinfection
function at least 4 hours later than the
last expected large hot water tapping.
This start-up can be set via the installer
settings (disinfection function).
When the Domestic hot water >
Type > Scheduled only is selected,
it is recommended to program a
Storage eco 3 hours before the
scheduled start-up of the disinfection
function to preheat the tank.
Do NOT press the
button while the
disinfection function is active.
Corrective action
Mount the communication cable
between the gas boiler and the indoor
unit properly.
Check the boiler display for error
information.
Corrective action
Make sure that the . setting is set to 0.
Update the boiler and hydrobox
software to the latest version.
Corrective action
Open the gas tap.
Remove air from the gas pipe.
Contact the gas supply company.