Siemens SIPROTEC 6MU805 User Manual page 40

Merging unit
Table of Contents

Advertisement

Functions
2.2 Merging Unit
At Address 0455A OptFlds refTime information, it is checked whether the field refresh time is contained in
IEC61850-9-2 telegram.
At Address 0456A OptFlds sam-syn, it is checked whether the field smpSynch is contained in IEC61850-9-2
telegram
At Address 0457A OptFlds samrate, it is checked whether the field smpRate is contained in IEC61850-9-2 tele-
gram.
Table 2-1 Relation of the detailed quality identifiers with invalid or questionable quality
DetailQuality
overflow
outOfRange
badReference
oscillatory
failure
oldData
inconsistent
inaccurate
Local Area Clock Identifier
Address 0485 IEC61850Ed2Sync informs the unique identifier of the specific local area clock if known, or 1 if
the identifier is not known. For example, 1 PPS input does not include the local area clock unique identifier,
and thus the specific local area clock is in general unknown.
Destination MAC Address
With Parameter 0486, 0487, 0488, 0489, 0490, 0491, you can configure the destination MAC address of the SV
telegrams respectively.
Application ID in IEC 61850
At address 0492 Application ID, you can select sample value messages and distinguish the application asso-
ciation.
36
Invalid
X
X
X
Questionable
X
X
X
X
X
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018