A.8
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
0104
OSC. FAULT REC.
0202
Vnom PRIMARY
0203
Vnom SECONDARY
0204
CT PRIMARY
0205
CT SECONDARY
0206A
Vph/Vdelta
0214
Rated Frequency
0217
Ignd-CT PRIM
0218
Ignd-CT SEC
0241
Volt.trans.A:C1
0242
Volt.trans.A:C2
0243
Volt.trans.B:C1
0244
Volt.trans.B:C2
0245
Volt.trans.C:C1
0246
Volt.trans.C:C2
0247
Volt.tran.Vx:C1
0248
Volt.tran.Vx:C2
0325
Vnom sec Vx
0333
Vnom prim Vx
0352
U4 inverting
0357
SV-Stop
0369
VT Con Type
0459
SysConMUConf
0461
PhaseIndepRatio
0403
MAX. LENGTH
0404
PRE. TRIG. TIME
0405
POST REC. TIME
0406
BinIn CAPT.TIME
0407
VLAN ID
0408
VLAN Priority
0438
PPS Delay
0460
PPS Synchro
0440A
Overflo Quality
0441A
OutRang Quality
0442A
BadRef Quality
0443A
Oscill Quality
0444A
Failure Quality
0445A
OldData Quality
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018
Function
Setting Options
Device Configuration
Disabled
Enabled
P.System Data 1
0.10 .. 800.00 kV
P.System Data 1
34 .. 400 V
P.System Data 1
10 .. 50000 A
P.System Data 1
1A
5A
P.System Data 1
1.00 .. 3.00
P.System Data 1
50 Hz
60 Hz
P.System Data 1
1 .. 50000 A
P.System Data 1
1A
5A
P.System Data 1
1.0 .. 100.0 pF
P.System Data 1
250 .. 10000 pF
P.System Data 1
1.0 .. 100.0 pF
P.System Data 1
250 .. 10000 pF
P.System Data 1
1.0 .. 100.0 pF
P.System Data 1
250 .. 10000 pF
P.System Data 1
1.0 .. 100.0 pF
P.System Data 1
250 .. 10000 pF
P.System Data 1
34 .. 230 V
P.System Data 1
0.10 .. 800.00 kV
P.System Data 1
YES
NO
Device Configuration
YES
NO
Device Configuration
Conventional
Cap. Volt.Meas.
Device Configuration
Disabled
Enabled
Device Configuration
Disabled
Enabled
Osc. Fault Rec.
0.30 .. 6.00 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
0.10 .. 5.00 sec; 
Osc. Fault Rec.
Merging Unit
0...4095
Merging Unit
1...7
Merging Unit
0 μs, 0.1 μs...5000.00 μs
Merging Unit
On
OFF
Merging Unit
False
Merging Unit
Set By MU
True
False
Merging Unit
False
Merging Unit
False
Merging Unit
Set By MU
True
False
Merging Unit
False
Default Setting
Disabled
Oscillographic Fault Records
20.00 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage (L-L)
400 A
CT Rated Primary Current
1A
CT Rated Secondary Current
1.73
Matching ratio Phase-VT To Open-Delta-VT
50 Hz
Rated Frequency
400 A
Ignd-CT rated primary current
1A
Ignd-CT rated secondary current
10.0 pF
Voltage transducer A: Capacity C1
2200 pF
Voltage transducer A: Capacity C2
10.0 pF
Voltage transducer B: Capacity C1
2200 pF
Voltage transducer B: Capacity C2
10.0 pF
Voltage transducer C: Capacity C1
2200 pF
Voltage transducer C: Capacity C2
10.0 pF
Voltage transducer Vx: Capacity C1
2200 pF
Voltage transducer Vx: Capacity C2
100 V
Rated Secondary Voltage Vx
20.00 kV
Rated Primary Voltage Vx
NO
U4 inverting
NO
SV-Stop
Conventional
Voltage Connection type
Disabled
MU Configuration via IEC61850 Configurator
Disabled
Phase Independent Ratio
2.00 sec
Max. length of a Waveform Capture Record
0.25 sec
Captured Waveform Prior to Trigger
0.10 sec
Captured Waveform after Event
0.50 sec
Capture Time via Binary Input
1
VLAN ID
4
VLAN Priority
0.0 μs
PPS Delay
ON
PPS Synchronization
False
Quality bit: Overflow
Set By MU
Quality bit: OutofRange
(Options True and False for test purpose)
False
Quality bit: BadReference
False
Quality bit: Oscillatory
Set By MU
Quality bit: Failure
(Options True and False for test purpose)
False
Quality bit: OldData
Appendix
A.8 Settings
Comments