2.1 General
Special Features
Most settings are self-explanatory. The special cases are described as follows:
At address 0369 VT Con Type, you can specify the connection type of the voltage inputs. If you are using normal
voltage transformers, select CONVENTIONAL.
With 0459 Syscon MU Configuration, you can define whether the communication parameter configured with
System configurator or not.
With 0461 PhaseIndepRatio, you can specify if the independent CT/VT ratio is supported for each channel.
Under address 0700 GOOSE-Stop, you can select whether the GOOSE function of the IEC 61850 protocol is
active or not. If GOOSE-Stop is set to YES, you can activate the GOOSE function via a binary input during the
operation.
Under address 0357 SV-Stop, you can select whether the SV function of the IEC 61850 protocol is active or not.
If SV-Stop is set to YES, you can activate the SV function via a binary input during the operation. The address
0357 SV-Stop is visible only when the address 0459 SysConMUConf is set as Enabled.

2.1.1.3 Settings

Addr.
0104
OSC. FAULT REC.
0357
SV-Stop
0459
SysConMUConf
0461
PhaseIndepRatio
0640
Start image DD
0700
GOOSE-Stop

2.1.1.4 Information List

No.
-
>Light on
-
Reset LED
-
DataStop
-
Test mode
-
Feeder gnd
-
Brk OPENED
18
Parameter
Setting Options
Disabled
Enabled
YES
NO
Enabled
Disabled
Enabled
Disabled
image 1
image 2
image 3
image 4
image 5
image 6
YES
NO
Information
Type of In-
formation
SP
IntSP
IntSP
IntSP
IntSP
IntSP
Default Setting
Disabled
NO
Disabled
Disabled
image 1
NO
Comments
>Back Light on
Reset LED
Stop data transmission
Test mode
Feeder GROUNDED
Breaker OPENED
C53000-G1140-C380-5, Release date 06.2018
Comments
Oscillographic Fault
Records
SV-Stop
MU Configuration via
IEC61850 System Con-
figurator
Phase Independent Ratio
Start image Default
Display
GOOSE-Stop
SIPROTEC, 6MU805, Manual