2.1 General
Table 4: Settings for 1-phase Ratio
Addr.
0481
0482
0483
0562
0563
0564
0565
0566
0567
0568
0569
0570
0571
0572
0573
0574
0575
26
Parameter
Setting Options
ClipV
1 .. 11
CurAccuClass
0.2/1 P
0.2 S/1 P
0.5/1 P
0.5 S/1 P
1/1 P
0.2/5 P
0.2 S/5 P
0.5/5 P
0.5 S/5 P
1/5 P
VolAccuClass
0.2/1 P
0.2 S/1 P
0.5/1 P
0.5 S/1 P
1/1 P
0.2/5 P
0.2 S/5 P
0.5/5 P
0.5 S/5 P
1/5 P
Ch1RatedPrimCur
10.. 25000 A
Ch1RatedSecCur
1 A
5 A
Ch2RatedPrimCur
10.. 25000 A
Ch2RatedSecCur
1 A
5 A
Ch3RatedPrimCur
10.. 25000 A
Ch3RatedSecCur
1 A
5 A
Ch4RatedPrimCur
10.. 50000 A
Ch4RatedSecCur
1 A
5 A
Ch1RatedPrimVol
0.10 .. 800.00 kV
Ch1RatedSecVol
34.. 400 V
Ch2RatedPrimVol
0.10 .. 800.00 kV
Ch2RatedSecVol
34.. 400 V
Ch3RatedPrimVol
0.10 .. 800.00 kV
Ch3RatedSecVol
34.. 400 V
Default Setting
2
Clip Voltage Limit
0.2/1 P
Current Accuracy Class
0.2/1 P
Voltage Acurrency Class
400 A
Channel1 Rated Primary
Current
1 A
Channel1 Rated Second
Current
400 A
Channel2 Rated Primary
Current
1 A
Channel2 Rated Second
Current
400 A
Channel3 Rated Primary
Current
1 A
Channel3 Rated Second
Current
400 A
Channel4 Rated Primary
Current
1 A
Channel4 Rated Second
Current
20.00 kV
Channel1 Rated Primary
Voltage
100 V
Channel1 Rated Second
Voltage
20.00 kV
Channel2 Rated Primary
Voltage
100 V
Channel2 Rated Second
Voltage
20.00 kV
Channel3 Rated Primary
Voltage
100 V
Channel3 Rated Second
Voltage
SIPROTEC, 6MU805, Manual