2.1.3.2 Setting Notes

Configuration
Fault recording (waveform capture) will only take place if address 0104 OSC. FAULT REC. is set to Enabled.
Other settings pertaining to fault recording (waveform capture) are found in the OSC. FAULT REC. submenu
of the SETTINGS menu.
The actual storage time begins at the pre-fault time PRE. TRIG. TIME (address 404) ahead of the reference
instant, and ends at the post-fault time POST REC. TIME (address 0405) after the storage criterion has reset.
The maximum storage time for each fault recording (MAX. LENGTH) is entered in address 0403. Recording
per event must not exceed 6 seconds. A total of 8 records can be saved. However, the total length of time of
all fault records in the buffer must not exceed 18 seconds.
An oscillographic record can be triggered by a status change of a binary input, or from a PC via the operator
interface. Storage is then triggered dynamically. The length of the fault recording is set in address 0406 BinIn
CAPT.TIMEbut not longer than MAX. LENGTH (address 0403). Pre-fault and post-fault times will add to this.
If the binary input time is set to , the length of the record equals the time that the binary input is activated
(static), but not longer than the MAX. LENGTH (address 0403).

2.1.3.3 Settings

Addr.
0403
MAX. LENGTH
0404
PRE. TRIG. TIME
0405
POST REC. TIME
0406
BinIn CAPT.TIME

2.1.3.4 Information List

No.
-
FltRecSta
4
>Trig.Wave.Cap.
203
Wave. deleted
30053
Fault rec. run.
2.1.4

Power System Data 2

2.1.4.1 Description

The general data (P.System Data 2) include parameters common to all functions, i.e. not associated with a spe-
cific monitoring function. In contrast to the P.System Data 1 before, they can be changed with the parameter
group.
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018
Parameter
Setting Options
0.30 .. 6.00 sec
0.05 .. 0.50 sec
0.05 .. 0.50 sec
0.10 .. 5.00 sec; 
Information
Type of Information
IntSP
SP
OUT_Ev
OUT
Default Setting
2.00 sec
Max. length of a Waveform
Capture Record
0.25 sec
Captured Waveform Prior to
Trigger
0.10 sec
Captured Waveform after Event
0.50 sec
Capture Time via Binary Input
Comments
Fault Recording Start
>Trigger Waveform Capture
Waveform data deleted
Fault recording is running
Functions
2.1 General
Comments
29