Siemens SIPROTEC 6MU805 User Manual page 29

Merging unit
Table of Contents

Advertisement

Table 3: Settings for 3-phase Ratio
Addr.
0480
0481
0482
0483
Table 4: Settings for 1-phase Ratio
Addr.
0214
0241
0242
0243
0244
0245
0246
0247
0248
0352
0369
0480
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018
Parameter
Setting Options
ClipC
1 .. 57
ClipV
1 .. 11
CurAccuClass
0.2/1 P
0.2 S/1 P
0.5/1 P
0.5 S/1 P
1/1 P
0.2/5 P
0.2 S/5 P
0.5/5 P
0.5 S/5 P
1/5 P
VolAccuClass
0.2/1 P
0.2 S/1 P
0.5/1 P
0.5 S/1 P
1/1 P
0.2/5 P
0.2 S/5 P
0.5/5 P
0.5 S/5 P
1/5 P
Parameter
Setting Options
Rated Frequency
50 Hz
60 Hz
Volt.trans.A:C1
1.0 .. 100.0 pF
Volt.trans.A:C2
250 .. 10000 pF
Volt.trans.B:C1
1.0 .. 100.0 pF
Volt.trans.B:C2
250 .. 10000 pF
Volt.trans.C:C1
1.0 .. 100.0 pF
Volt.trans.C:C2
250 .. 10000 pF
Volt.tran.Vx:C1
1.0 .. 100.0 pF
Volt.tran.Vx:C2
250 .. 10000 pF
U4 inverting
YES
NO
VT Con Type
Conventional
Cap. Volt.Meas.
ClipC
1 .. 57
Default Setting
20
Clip Current Limit
2
Clip Voltage Limit
0.2/1 P
Current Accuracy Class
0.2/1 P
Voltage Acurrency Class
Default Setting
50 Hz
Rated Frequency
10.0 pF
Voltage transducer A: Capacity
C1
2200 pF
Voltage transducer A: Capacity
C2
10.0 pF
Voltage transducer B: Capacity
C1
2200 pF
Voltage transducer B: Capacity
C2
10.0 pF
Voltage transducer C: Capacity
C1
2200 pF
Voltage transducer C: Capacity
C2
10.0 pF
Voltage transducer Vx: Capacity
C1
2200 pF
Voltage transducer Vx: Capacity
C2
NO
U4 inverting
Conventional
Voltage Connection Type
20
Clip Current Limit
Functions
2.1 General
Comments
Comments
25

Advertisement

Table of Contents
loading

Table of Contents