Technical Data
4.2 Additional Functions
Fault Recording
max. 8 fault records saved by buffer battery also in the event of auxiliary voltage failure
Storage period
Sampling rate at 50 Hz
Sampling rate at 60 Hz
Operating Hours Counter
Display range
Criterion
Commissioning Aids
- Operational measured values
- Creating a test fault record
- Generating indications
- Controlling transmission IEC 61850-8-1 GOOSE messages
- Controlling transmission IEC 61850-9-2 Sample values
- Controlling transmisssion IEC 61850-9-2 Sample values quality bit
- PPS/IRIG-B signal status indication
- SV synchronization status indications
Clock
Time synchronization
Operating modes of the clock management
Operating mode
Internal Clock
IRIG-B
GPS
SNTP
IEC 61850 GOOSE (Inter-Device Communication)
The GOOSE communication service of IEC 61850 is qualified for switchgear interlocking. Since the transmis-
sion time of GOOSE messages depends on both the number of IEC 61850 clients and the pickup condition of
the device, GOOSE is not generally qualified for protection-relevant applications. The protection application
must be checked with regard to the required transmission times and coordinated with the manufacturer.
118
6 s per fault record, in total up to 18 s at 50 Hz
(max. 15 s at 60 Hz)
each 1 instantaneous value per 1.0 ms
each 1 instantaneous value per 0.83 ms
up to 7 decimal places
Exceeding an adjustable current threshold (CB I>)
Binary input
Communication
IRIG-B Signal
Comments
Internal synchronization via RTC (default)
External synchronization via IRIG-B
External synchronization via GPS
External synchronization via Ethernet Interface
C53000-G1140-C380-5, Release date 06.2018