Set the unit on mounting brackets or pad.To avoid the adverse effects of snow, ice and defrosting issues, install
the unit on heat pump risers to ensure a sufficient height from the ground . In all cases, refer to local code for
correct riser height .
Make sure the outdoor unit is installed level and is stable .
Install snow protection hood as necessary .
Precautions on
installation
Notice
If drain holes of the outdoor unit are covered by a mounting base or by floor surface, raise the unit in order
to provide a free space of more than 130mm under the outdoor unit.
Correct installation
Drainage
Correct installation
Minimum height (H) should be
higher than the highest snowfall
depth (D) (H=D+20cm)
Wrong installation
Drainage
Clearance is too
stand to is
small, causing
covered
inadequate drainage.
Wrong installation
unit may become covered in snow
if the stand height is insufficient.
Drainage