Indoor
Malfunction Description
code
display
19 F19
DC voltage or AC voltage low
Indoor pipe temperature too high
20 F20
protection
Indoor pipe temperature
21 F21
sensor too low protection
22 F22
PFC circuit loop overcurrent
Temperature too high for
23 F23
compressor driver module
24 F24
Compressor start failure
Input overcurrent of the drive
25 F25
module
26 F26
Lack phase of the drive module
27 F27
Input current sampling circuit fault The driver module's input current sampling circuit damaged
28 F28
No wiring of the compressor
Compressor overcurrent detected
by
37 F37
compressor driver module
Drive module's ambient temp.
38 F38
sensor abnormal
Mid-condenser temp. sensor TC
39 F39
abnormal
Outdoor condenser
44 F44
temperatureTC too high protection
45 F45
System low pressure protection
1. 4TXK6536G1000AA:
The outdoor control board's LED1 and LED2 indicates the outdoor error code. for example,the error code 12,
LED1 will flashing 1 and LED2 will flashing 2,alternating flashing.
4TXK6548G1000AA.4TXK6560G1000AA:
The outdoor control board's LED3 indicates the outdoor error code. for example,the error code 12, LED3 will
display 12 and keep flashing.
2.NO-resumable means error will not clear unless:a. clean out the fault factor b. Cut the power supply off and re-
offer again after point a achieved.
3. The indoor unit can also indictes the outdoor malfuction code too. Please refer to indoor unit manul or indoor
trouble shooting to get the method .
Diagnosis and Analysis
AC power supply of the driver module get voltage lower
than 155VAC (1phase)or driver module get high DC-BUS
voltage lower than 180VDC
Indoor pipe temperature Tm over 63°C, error clear within 3
minutes. if temperature goes down and lower than 52°C.
Indoor pipe temperature too low, outdoor unit stop toprevent
indoor heat exchange system icing and to prevent the indoor
unit outlet air too low at the same time.
Overcurrent been detected in power factor correction circuit
loop.
Compressor driver module's PIM temperature over 90°C, Error
stat-us lock if it occurs 3 times in 1 hour.
Compressor start failure been detected by driver driver module
or wrong compressor wiring
Input current of the compressor drive module higher than
EEPROM setting(details refer to service manual) Lock if
occurs 3 times in 1 hour
Lack phase of the drive module's power supply (three
phase type)
No wiring between compressor and it's driver module
Compressor phase U or V or W over current detected by
compressor driver module (details refer to service manual)
The temperature detected is not within the range of -25°C to
150 °C
The temperature detected is not within the range of -55°C to
90 °C
The maximum temperature value of Tc and T e is over 65 °C,
Error lock if it occurs 3 times in 30 minutes
The minimum temperature value of indoor pipe Tm and
outdoorT s is lower than-45 °C at cooling mode or minimum
temperature value of outdoor Tc and outdoor T e is lower than-
45 °C at heating mode
151