Koolman500 air-cooled cold generator with heat pump option (32 pages)
Summary of Contents for Trane 4TYK6524D1000AL
Page 1
Installation, Operation and Maintenance Manual U-Match DC Inverter System R-410A Up To 16 SEER Outdoor Unit - Cooling Only and Heat Pump 24,000 to 60,000 BTU/h - 60Hz Cooling Only Heat Pump 4TYK6524D1000AL 4TXK6524D1000AL 4TYK6536D1000AL 4TXK6536D1000AL 4TYK6548D1000AL 4TXK6548D1000AL 4TYK6560D1000AL 4TXK6560D1000AL MCX05...
Content Identification ............5 Unit Installation .
Page 3
Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Page 4
Warnings, Cautions and Notices WARNING Personal Protective Equipment (PPE) Required! Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical and chemical hazards, MUST follow precautions in this manual and on the tags, stickers and labels, as well as the instructions below: •...
Identification Identification U-Match Inverter Unit (16 SEER) - R410A Refrigerant Voltage 220/230/1/60hz Outdoor Unit - Cooling Only Model Capacity 4TYK6524D1000AL 24 MBH - 16 SEER 4TYK6536D1000AL 36 MBH - 16 SEER 4TYK6548D1000AL 48 MBH - 16 SEER 4TYK6560D1000AL 60 MBH - 16 SEER...
Page 6
Identification Figure 1. Filter Dryer Installation It is better to open de service valve after the removal of the bottom access panel Large service valve Small service valve Liquid line filter dryer . Field provided and installed Limitations The unit should be installed in accordance with all national, state and local codes and in compliance with the following limitations: 1.
Page 7
Identification Figure 2. Dimensional Data DISCHARGE AIR: ALLOW 60” (1.5m) MINIMUM CLEARANCE INCOMING AIR DAMPER WITH VENTS: SERVICE ACCESS ALLOW 18” (0.45m) ALLOW 24” MINIMUM MINIMUM CLEARANCE CLEARANCE NOTE: GRILL APPEARANCE MAY VARY POWER WIRING SEE DETAIL A CONTROL WIRING DETAIL A 7/8”...
Unit Installation Unit Installation Location Prior to the installation, select and verify the adaptability of the location for both indoor and outdoor units. Take into consideration all limitations and clearance requirements. The outdoor unit must comprise sufficient clearance for incoming air into the condenser, for discharge air, and for service access.
Page 9
Unit Installation Mounting of the Unit If the unit is to be installed on a roof surface or on a concrete base, observe the following guidelines: 1. The provided base pan rises the heating pump 2” above the installation base. 2.
Page 10
Unit Installation IMPORTANT NOTE: These instructions are intended to provide a method of installation of the unit to the concrete base in order to establish a protective procedure in cases of strong winds. It is recommended to verify local codes for the application of methods and protocols for secure setting of the unit. Figure 4.
Page 11
Unit Installation Figure 5. Lines Support Suggested Sheet metal support Insulated suction line Insulation optional Wrong Insulated liquid line Figure 6. Underground Installation A unidad exterior A serpentín interior Línea liquido Tapa Línea vapor aislada Figure 7. Typical Installation Disconnect switch To power supply indoor...
Page 12
Unit Installation Precautionary Measures During Line Brazing All connections to indoor unit and to evaporator coil will be copper-to-copper. Brazing material should be done with the use of a copper-phosphorous alloy such as Silfos-5 or equivalent. DO NOT employ soft brazing alloy. Outdoor units contain service valves in both liquid and suction connections.
Page 13
Unit Installation 4. Replace the Schraeder core once more onto the liquid and suction valves. 5. Carry out leak tests on all refrigerant line connections, including tapered valves at the service port to ensure they are all leak-free. DO NOT OVERTIGHTEN (between 40 and 60 in.lbs maximum).
Page 14
Unit Installation Figure 9. Piping Length Diagram #1 Outdoor Indoor units units Rise Rise Always use the shortest length possible with a minimum amount of curves. Note: Excessively long refrigerant lines produce capacity loss for the equipment. Vertical Rise Keep the vertical rise at a minimum. See the following guides for unit installation. 1.
Page 15
Unit Installation Installation of TXV Valve TXV Kit (thermostatic expansion valve) provided together with the equipment is for on-site mounting. Installation of this valve must be done with tapered threaded fitting. Figure 10. Thermostatic Expansion Valve TXV Figure 11. Steps for TXV Kit Installation SETP 1 Tapered Brazed...
Page 16
Unit Installation Evacuation It is required to evacuate the system at 350 microns or less. If a leak is suspect, apply dry nitrogen to locate it. Repair the leak and repeat the leak test. To verify that the system reports no further leaks, close the valve that goes to the suction vacuum pump;...
Electrical Connections Electrical Connections General Information and Grounding Verify power supply to ensure compliance with data on the unit’s identification label and wiring tags. The installer shall supply power wiring, control wiring (low voltage), disconnect switches and overcurrent protection. All cable wiring should comply with specific requirements. CAUTION! All field wiring shall be of ONLY COPPER CONDUCTORS and in compliance with local, national and electrical security codes.This unit must be grounded with a separate cable and in accordance with local, national and...
Page 18
Electrical Connections Figure 13. Removal of top panel and motor 1/2” nut NOTE: 5/16” nuts If fan nuts are removed before removal of top panel, it will harm the condensing unit. When it is necessary to change the motor, follow the steps indicated below: Step 1: Open the electrical panel;...
System Operation System Operation Control Logic Description The variable speed system adopts the same 24VAC control as conventional heat pumps. Compressor speed is controlled according to coil pressures monitored by the pressure transducer. In order to ensure stable and appropriate capacity, compressor speed is modulated in accordance with evaporator pressure during the cooling mode, and in accordance with condensing pressure during the heating mode.
Page 20
System Operation Tf sensor is required for: – Protection against module temperature (high temperature) A pressure transducer (PT) is required for: – Operating speed control – Outdoor electronic expansion valve (heat pump only) – High pressure protection (heating mode heat pump only) –...
Page 21
System Operation Defrost Options SW5-1 SW5-2 Remarks Operating time Defrost is reduced by extended by 60 seconds Normal Normal Default Remarks Enter defrost Cancel defrost Manual Defrost (Heat Pump Only) 1. Demand defrost can start when the system has been operating in heating mode during a period exceeding 8 minutes.
Page 22
System Operation Protection Functions Outdoor coil protection function (T3) – When T3 ˃ 143.6ºF, compressor stops working – When T3 ˃ 129.2ºF, compressor starts working Ambient temperature protection (T4) – When 40ºF ≤ T4 ˂ 120ºF, the unit is able to operate in the cooling mode –...
Page 23
System Operation Refrigerant Charge Review Weigh-in Method (use of electronic scale) Weigh-in method can be used the initial installation or anytime a system charge is being replaced. This method can also be used when power is not available at the site, or when operating conditions (indoor/outdoor temperature) are not in range to verify with the sub-cooling charging method.
Page 24
System Operation Sub-cooling charge and refrigerant adjustment during cooling mode (above 55ºF outdoor temperature) MS-SVN052E-EN...
Page 27
System Operation Final Leak Test After evacuating and charging the unit, use a halogen detector to detect any leaking. All piping must be verified in the evaporator, in the condenser and in the interconnecting lines. If a leak is detected, all refrigerant must be recovered before any intent of repair is carried out.
Wiring Diagrams Wiring Diagrams CAUTION! These units must be wired and installed in compliance with all national, state and local security codes. Figure 14. Outdoor Unit Wiring for A/C Systems (208/230V/1 Phase- 60Hz) MS-SVN052E-EN...
Page 29
Wiring Diagrams Figure 15. Control Wiring Diagram for A/C Systems Post description C1: Compressor N1: Common 24 VAC C: Common 24 VAC Y: Compressor (Outdoor Unit) Grounding (Indoor Unit) Figure 16. Control Wiring Diagram for Heat Pump Systems Post description C1: Compressor N1: Common 24 VAC V1: 4-way valve...
Page 32
Troubleshooting Operational and Verification Procedures Parameter Point Check Table Press “Check” button to see system available parameters. When pressing for the first time, the display will show you a sequence and at the end of 1 minute, the parameter value will appear. When pressing a second time, the following sequence appears.
Page 33
Troubleshooting For model 24/36k MS-SVN052E-EN...
Page 34
Troubleshooting For model 48/60k and board Board MS-SVN052E-EN...
Page 36
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency.