10.7 4TXK6518G1000AA failure code
LED flash
times of
Indoor
Contents of Malfunction
outdoor
display
PCB
1
F1
EEPROM fault
2
F2
IPM protection
Communication between
4
F4
main board and power
module
5
F5
High pressure protection
Power module over/lack-
6
F6
voltage protection
Compressor Td temp.
8
F8
protection
9
F9
DC fan motor fault
10
F10
Abnormal of coil sensor
Suction temperature sensor Suction temperature sensor short-circuit or open-circuit or the
11
F11
failure
Outdoor ambient sensor
12
F12
fault
13
F13
Compressor Td sensor fault Compressor Td sensor short-circuit oropen-circuit
Communication between
15
F15
indoor and outdoor unit
16
F16
Lack of refrigerant
17
F17
4-way valve reverse failure
18
F18
Compressor jam
Power module PWM select
19
F19
circuit fault
Compressor U-phase over-
25
F25
current
Compressor V-phase over-
25
F25
current
Compressor W-phase over-
25
F25
current
Diagnosis and Analysis
EEPROM chip damaged or data fault
Input overcurrent occured been detected by PIM hardware
Communication fail over 4 min
System high pressure over 4.15Mpa
Send from power module
Compressor Td temp. over 110°C
Jam of DC motor or motor fault
Coil sensor short-circuit or open-circuit
compressor connection is poor
Outdoor ambient sensor short-circuit or open-circuit
Communication fail over 4min
Check if there is leakage in the unit
Alarm and stop if detect Td-Tci≤15 last for 1 min after
compressor has started for 10 min in heating mode, confirm the
failure if it appears 3 times in one hour.
Compressor jamed internally
Power module PWM selects wrong circuit
The current of compressor U-phase is too high
The current of compressor V-phase is too high
The current of compressor W-phase is too high
148