Drain Pipe
processed as specified in the installation manual and shall be thermal insulated to avoid dew generation.
lmproper hose connection may cause indoor water leakage.
Requirements
 The indoor drain pipe shall be thermal insulated .
 The connection part between the drain pipe and the indoor unit shall be insulated so as to prevent dew generation.
 The drain pipe shall be slant downwards (greater than 1/100).The middle part shall not be of S type
elbow, otherwise abnormal sound will be produced .
 The horizontal length of the drain pipe shall be less than 20 m.ln case of long pipe, supports shall be
provided every 1 .5 _ 2m to prevent wavy form .
 Central piping shall be laid out according to the right figure .
 Take care not to apply external force onto the drain pipe connection part .
 For unit with water pump drain pipeuse hard PVe general purpose pipe VP which can be purchased locally . When
connecting, insert a PVe pipe end securely into the drain socket before tightening securely using the attached drain
hose and clamp . Adhesive must not be used for connection of the drain socket and drain hose (accessory) .