5.2.2

Installation of a master device file (GSD)

The device description for the frequency converter is declared to HW Config in STEP 7 by
installing the GSD (master device file) for use with PROFIBUS and the GSDML for use with
PROFINET. If no HSP is installed for the frequency converter in the STEP 7 pack, or if the
frequency converter is operated with a third party master, the device description for
operation on PROFIBUS can be implemented by installing the GSD file. In this case the
masks and the designation of the frequency converters differ from the S7 standard as
described on the following page.
The following example demonstrates how the GSD can be input into HW Config of the
SIMATIC.
● Open the program "HW Config".
Close any projects which may be open there.
● Then select Options > Install GSD files in order to open the dialog box for installing GSD
files and click "Browse" to select the location of the GSD file.
● Then select the file you want from the list and click on the button "Install".
After the dialog is closed, the hardware configuration catalog is updated automatically
and you can open your project.
● Install the GSD file in the required language (English, French, German, Italian, or
Spanish) from the folder containing the relevant data.
● Selection of the telegram in the frequency converter is set using the parameter P0922
while the drive is commissioned. The receive telegram is in r2050[8] and the send
telegram is set using the P2051[8] parameter.
ET 200pro FC
Operating Instructions, 07/2016, A5E01100763B AC
5.2 Installation of the hardware information in SIMATIC Manager
Configuration / project engineering