Et 200S Fc Frequency Converter In The Industrial Environment; 200Pro Fc Frequency Converter In A Drive System In Accordance With En 61800-3 - Siemens Simatic ET 200pro FC Operating Instructions Manual

Table of Contents

Advertisement

Appendix
A.2 ESD directives
A.2.4

ET 200S FC frequency converter in the industrial environment

ET 200pro FC frequency converters with integrated Class A EMC filters are designed for use
in an industrial environment, provided that the permissible cable lengths are used.
Table A- 9
Fields of application
Industry
Installation guideline for ET 200pro FC frequency converter with integrated EMC filter
● Operation is only permitted for TN line supply systems.
● The converter must be assembled on a grounded plate with a large surface.
● The module rack is to be grounded.
● The maximum length per frequency converter of the shielded power cable is 15 m.
A.2.4.1
ET 200pro FC frequency converter in a drive system in accordance with EN 61800-3
Explanatory notes for EN 61800-3+A11
The EN 61800-3+A11 product standard for "Adjustable speed electrical power drive
systems, Part 3: EMC requirements and specific test methods" specifies limit values for
noise radiation and interference immunity. The EMC product standard EN 61800-3+A11
does not apply directly to a frequency converter but to a complete drive system, which
comprises the complete circuitry, motor and cables in addition to the converter.
Limit values for compliance with EN 61800-3 Category C3
The following table lists the key limit values for compliance with EN 61800-3 on devices with
restricted availability for a drive system in accordance with Category C3 (Category C3: Drive
system (PDS) with a rated voltage of < 1000 V. For use in a second environment), i.e., use
in second environment (industrial) with commissioning and installation carried out by an
EMC expert.
Table A- 10
EMC phenomena
Radiated emissions
Conducted emissions
176
Use in the industrial environment
Emitted noise
EN 61000-6-4, with Class A filter
Limit values for noise radiation for a drive system compliant with Category C3
Basic standard
for test proce-
dures
EN 55011
EN 55011
Requirement for
Interference immunity
Limit value
Class A, Group 1
Class A, Group 2
Operating Instructions, 07/2016, A5E01100763B AC
EN 61000-6-2
ET 200pro FC

Advertisement

Table of Contents
loading

Table of Contents