E8F2
Bar Indicator Range Setting
The set value is an indication range per LED between 1 and 20% FS. If the E8F2 is set to AUT, the ideal display range will be automatica
set according to the the ON point presently set.
OUT1 OUT2
kPa Torr Psi
or
1. Press the SET key while bar is displayed to display the bar display range presently set.
2. Press the Up or Down key to change the set value.
3. Press the SET key to select the displayed set value and display bar again.
4. Press the Up and Down keys simultaneously to display bar again without selecting the set value.
Note: The bar indicator range will be available to OUT1 output and will be enabled in hysteresis mode only.
Bar Indicator
The user can visually sense the measured pressure according to the ON and OFF points from the bar indicator. This indicator is avail-
able to OUT1 output only. There is a difference in indication mode between hysteresis mode and window mode.
Hysteresis Mode
The five LEDs indicate the present pressure provided that the ON point is between the second and third LEDs from the left.
1-MPa Model (with 300 kPa as ON Point)
ON
Condition 1 (350 kPa)
OFF
300
(ON point)
The indication range per LED is obtained from the following.
300 kPa ≤ 1 MPa x 1/2
300 kPa x 1/3 = 100 kPa
The first through third LEDs from the left are all ON under condition 1. The indication range per LED is the set value of the indication
range in special setting mode. If the set value is aut, the following ranges are obtainable.
When ON point ≤ Rated pressure x 1/2
Indication range per LED = ON point x 1/3
When ON point > Rated pressure x 1/2
Indication range per LED = (Rated value - - ON point) x 1/3
Window Mode
The distance between ON and OFF points are divided into five equal portions. The present pressure will be indicated by a single
LED that will be ON. The left LED will flash if the present pressure is below the ON point and the right LED will flash if the present
pressure is above the OFF point.
1-MPa Model
(with 300 kPa as ON point and 600 kPa as OFF point)
ON
Condition 2
(450 kPa)
OFF
300 kPa
(ON point)
OUT1 OUT2
kPa Torr Psi
Press Up or Down key to
change set value.
Pressure
value: kPa
Condition 3
(700 kPa)
Pressure
600 kPa
value: kPa
(OFF point)
Only LED (a) will be lit under condition 2.
Only LED (b) will be lit under condition 3.
The display range per LED will be the following.
Difference between ON and OFF points x 1/5
Note: No bar indicator settings in special setting mode will be enabled
19
E8F2