Omron V600-CA8A-V Series Operation Manual page 59

Parallel interface id controller
Table of Contents

Advertisement

Operation Test (TEST)
4-5-4 Test Auto Write
Operation Procedure
1, 2, 3...
One byte of data is written repeatedly to any memory area defined by specified
start and end addresses from the DC while it is in motion. The step number of the
send data can be set to any value in the range 1 to FF (256 bytes maximum),
enabling a total communications test checking relationships between installa-
tion positions, speeds, and other parameters.
This example shows the procedure for writing FF into locations 10 to 20.
Job specification
(Head no. and page no)
ADRS
RESET
1
0
ADRS
2
0
F
F
DATA
TEST 1 4
TEST
TAW
4
When operation is OK
TAW
Test auto write
display
(Cancel operation by pressing
1. Specify the start address.
2. Specify the end address.
3. Specify the data.
4. When the TEST Key is pressed, the test menu is shown on the display.
a
dXX
_
(1)
a10dXX
a
dXX
_
(2)
a20dXX
a20dFF
(3)
(4)
(5)
dFF
(6)
Data
)
RESET
Section
4-5
55