Configuration and startup
Verify that the following switch settings are correct for your transmitter installation:
SW3: The factory sets this switch as follows:
Positions 3 and 4 must be set up as shown for proper software control of the device
heaters.
3.2

Initial power up

Allow adequate time (approximately 60 minutes) for the heaters to begin operation and
for the transmitter to reach normal operating temperature on power up.
Normal operating temperature for the O
temperature for the combustibles cell is 300 °C (573 °F). The normal sample line
temperature is 170 °C (443 °F). During this time, the eductor air solenoid remains closed so
no sample is pulled through the analyzer. When the transmitter reaches operating
temperatures, the solenoid energizes, eductor air begins to flow, and the unit begins
normal operation.
3.3

Set test gas values

Use Field Communicator or the optional LOI to set test gas values for calibration. Refer to
Section
3.3.1

Setting test gas values with the Field Communicator

Complete the following steps to set test gas values with the Field Communicator.
1.
2.
3.
4.
5.
6.
7.
8.
3.3.2

Setting test gas values with Fieldbus communicator

Complete the following steps to set test gas values with Fieldbus communicator.
46
Position 1 not used.
Position 2 not used.
or
Section 3.3.2
for more information.
Use the 375 Field Communicator to access the HART menu.
From the DETAILED SETUP menu, select CAL SETUP.
From the CAL SETUP menu, select O2 CAL PARAMS or COe CAL PARAMS.
From the DETAILED SETUP menu, select O2 CAL PARAMS.
From O2 CAL PARAMS, select O2 HIGH GAS. Enter the percent O
O
test gas.
2
From O2 CAL PARAMS, select O2 LOW GAS. Enter the percent O
test gas.
From the DETAILED SETUP menu, select COe CALIB PARAMS.
From COe CAL PARAMS, select COe Test Gas. Enter the CO concentration (ppm) used
for COe test gas.
cell is 736 °C (1357 °F) . Normal operating
2
used for the high
2
used for the low O
2
2