Table 7-29:
Troubleshooting
Symptom
Mode will not leave IMAN.
Mode will not change to AUTO.
Mode will not change to CAS.
Mode sheds from RCAS to AUTO.
Reference Manual
(continued)
Possible causes
4. Schedule
Back calculation
1. Target mode not set
2. Input
1. Target mode not set.
2. Cascade input
1. Remote cascade value
2. Shed timer
Foundation Fieldbus
Corrective action
4. Block is not scheduled and there-
fore cannot execute to go to Target
mode. Schedule the block to execute.
BKCAL_IN
a. The link is not configured (the status
would show Not connected). Con-
figure the BKCAL_IN link to the down-
stream block.
b.The downstream block is sending
back a Quality of Bad or a Status of
Not Invited. See the appropriate
downstream block diagnostics for cor-
rective action.
1. Set target mode to something oth-
er than OOS.
2. IN
a. The link is not configured (the status
would show Not connected). Con-
figure the IN link to the block.
b.The upstream block is sending back
a Quality of Bad or a Status of Not
Invited. See the appropriate up-
stream block diagnostics for correc-
tive action.
1. Set target mode to something oth-
er than OOS.
2. CAS_IN
a. The link is not configured (the status
would show Not connected). Con-
figure the CAS_IN link to the block.
b.The upstream block is sending back
a Quality of Bad or a Status of Not
Invited. See the appropriate up-
stream block diagnostics for correc-
tive action.
1. Host system is not writing RCAS_IN
with a quality and status of good
cascade within shed time (see 2 be-
low).
2. The mode shed timer, SHED_RCAS,
in the resource block is shed too low.
Increase the value.
171