Hardware maintenance tools

Contents

This section contains the following topics:
"Introduction" (page 29)
"Alarm/fan module features" (page 29)
"Compact flash cards" (page 32)
"Circuit card features" (page 33)
"Signaling servers for DTLS" (page 52)
"System alarms" (page 53)
"Line transfer" (page 54)
"External power loss" (page 55)

Introduction

Fault indicators and hardware features help perform maintenance tasks
(particularly identifying and clearing faults). These maintenance tools
include:
circuit card features that include self-tests and status indicators
LED indicators that identify Call Server power and temperature faults
system alarms that categorize the severity of component failure

Alarm/fan module features

The NTDU64 alarm/fan module provides cooling for a CP PIV Call
Processor. It also provides a thermostat to monitor the Call Server
temperature.
If the Call Server temperature reaches 42 C (107 F), the fan units switch
into high-speed mode. The fans revert to normal speed when the Call
Server temperature falls below 37 C (98 F). Also, if one fan fails, the
remaining two fans switch into high-speed mode indefinitely.