*1 – Voltage drop across power cables not to exceed 2% of nominal source voltage.
*2 – Allowable ampere-capacities based on copper conductors with 75°C. insulation at ambient temperature of 40°C.
*3 – If using different cable type, rating, or in different site conditions, ensure that adjusted ampacity is equal to or larger than the sizes listed in the table.
*4 – Sized based on necessary overcurrent protection for maximum load.
UPS Capacity
Bolt size
500kVA
M12 x 40mm
750kVA
M12 x 40mm
42
Table 5-4 Recommended Cable Sizes
Input Side
Cable
Torque
Size
in. lbs
7 x 300MCM
347 - 469
6 x 300MCM
or larger
in. lbs
7 x 350MCM
347 - 469
7 x 350MCM
or larger
in. lbs
Table 5-5 Recommended Hardware
Split
Flat washer
lockwasher
size
size
M12
M12
M12
M12
G2020 Series UPS Installation and Operation Manual – 94861-004