Code
LCD Screen Status
indication
Message
(Note 3)
INVERTER
UF217
OVERVOLTAGE
ZERO PHASE
UF230
OVERCURRENT
UPS CONTROL
UF253
CIRCUIT ERROR
OUTPUT VOLTAGE
UF256
ABNORMAL
UF257
52C ABNORMAL
UF258
LOAD ABNORMAL
ANOTHER UPS
UF259
ABNORMAL
UPS CONTROL
UF301
CIRCUIT ERROR
UPS CONTROL
UF302
CIRCUIT ERROR
UPS CONTROL
UF303
CIRCUIT ERROR
UPS CONTROL
UF305
CIRCUIT ERROR
UPS CONTROL
UF306
CIRCUIT ERROR
INVERTER
UF309
VOLTAGE
ABNORMAL
CONTROL POWER
UF310
SUPPLY
ABNORMAL
UPS CONTROL
UF320
CIRCUIT ERROR
UPS CONTROL
UF323
CIRCUIT ERROR
UPS CONTROL
UF331
CIRCUIT ERROR
UPS CONTROL
UF332
CIRCUIT ERROR
UPS CONTROL
UF333
CIRCUIT ERROR
UF334
UPS CONTROL
CONTROL POWER
UF352
SUPPLY
ABNORMAL
UPS CONTROL
UF363
CIRCUIT ERROR
UPS CONTROL
UF371
CIRCUIT ERROR
UPS CONTROL
UF372
CIRCUIT ERROR
UPS CONTROL
UF374
CIRCUIT ERROR
UPS CONTROL
UF375
CIRCUIT ERROR
UPS CONTROL
UF376
CIRCUIT ERROR
UPS CONTROL
UF377
CIRCUIT ERROR
UPS CONTROL
UF378
CIRCUIT ERROR
UPS CONTROL
UF379
CIRCUIT ERROR
G2020 Series UPS Installation and Operation Manual – 94861-004
Meaning
Detection of inverter output phase
overvoltage.
Detection of zero-sequence
overcurrent.
Discrepancy between output voltage
and inverter voltage, or between
output voltage and bypass voltage.
Output voltage is out of the specified
range.
Contactor 52C failed to open during
load transfer from inverter to
bypass.
Load transfer due to overload for
over 4 times within 5 minutes.
No detection of another UPS voltage
signal.
AD reference has an abnormal
value.
Detection of an external interruption
during the software execution.
Timer does not reset in the specified
period (WDT settings)
Detection of an abnormal clock
speed in the DSP or FPGA.
Control power supply voltage is
below the specified level.
Inverter voltage is out of the
specified range.
Backup control power supplies
exhibit abnormal condition.
Cable disconnection in the parallel
interface board during load supply.
Major communication error during
parallel operation.
Major abnormal detected in the
converter unit
Major abnormal detected in the
inverter unit
Major abnormal detected in the
chopper unit
Major abnormal detected in
Backup control power supplies
exhibit abnormal condition.
Synchronization status signal is
being received for a considerable
time.
Minor communication error during
parallel operation.
Unable to synchronize the inverter
output and the bypass voltage.
Cable disconnection in the parallel
interface board.
Unable to achieve synchronization
for parallel operation.
No control response from another
UPS although its detection is
possible.
Overload detection signal is being
received continuously for a
considerable time.
No answer for sending
synchronizing signal.
Abnormal clock speed of the parallel
control board processor.
Recommended
Buzzer
Action
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittentsou
ENGINEER
nd
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
External relay
Failure
contact
lamp
(Note 1)
(Note 2)
Major
Cont. On
Major
Cont. On
Minor
Blinking
Minor
Blinking
Minor
Blinking
Minor
Blinking
Minor
Blinking
Major
Cont. On
Major
Cont. On
Major
Cont. On
Major
Cont. On
Major
Cont. On
Major
Cont. On
Major
Cont. On
Major
Cont. On
Major
Cont. On
Major
Cont. On
Major
Cont. On
Major
Cont. On
Major
Cont. On
Minor
Blinking
Minor
Blinking
Minor
Blinking
Minor
Blinking
Minor
Blinking
Minor
Blinking
Minor
Blinking
Minor
Blinking
Minor
Blinking
Minor
Blinking
65