Toshiba G2020 Series Installation And Operation Manual page 74

480/480 v 500kva/750kva
Hide thumbs Also See for G2020 Series:
Table of Contents

Advertisement

Code
LCD Screen Status
indication
Message
(Note 3)
UF401
52S ABNORMAL
UF402
52S ABNORMAL
52L OPERATION
UF420
ERROR
UF451
52S ABNORMAL
UF452
CB3 ABNORMAL
(Note 1) 1) "Major" is defined as a major failure. Load transferred from the inverter circuit to the static bypass line;
2) "Minor" is defined as a minor failure. UPS continues to operate normally, but cause of alarm is identified;
(Note 2) Indicates one of two possible LED illumination patterns – continuously on (Cont. On) or intermittent (Blinking).
(Note 3) Code indication means:
UA+++ ------------------------ Alarm
UF+++ ------------------------ Failure
U%0++ ----------------------- Rectifier circuit failure
U%1++ ----------------------- DC circuit failure
U%2++ ----------------------- Inverter circuit failure
U%3++ ----------------------- Control circuit failure
U%4++ ----------------------- Bypass system failure
U%8++ ----------------------- Alarm
U%+00 - U%+49 --------- Major failure
U%+50 - U%+99 --------- Minor failure
*) "+" denotes any numeral from 0 to 9
*) "%" denotes either "A" or "F"
66
Meaning
Error to close the contactor 52S.
Error to open the contactor 52S.
Load circuit breaker 52L opened
during inverter operation.
Contactor 52S failed during load
transfer from inverter to bypass.
Contactor CB3 is not working
properly.
G2020 Series UPS Installation and Operation Manual – 94861-004
Recommended
Buzzer
Action
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
Continuous
CHECK 52L
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
External relay
Failure
contact
lamp
(Note 1)
(Note 2)
Major
Cont. On
Major
Cont. On
Major
Cont. On
Minor
Blinking
Minor
Blinking