Cable Ups To Battery Cabinet(S); Figure 5 Cabling 8/10Kva Ups To Battery Cabinet - Toshiba 1600XPi Series Installation And Operation Manual

8-22kva battery cabinet
Hide thumbs Also See for 1600XPi Series:
Table of Contents

Advertisement

4.2

Cable UPS to Battery Cabinet(s)

Connect up to two (2) battery cabinets to the UPS as shown in Figure 3 and Figure 4.
1. Ensure all power is locked and tagged out.
2. Remove the battery connector cover mounted on the UPS back panel.
To connect the first battery cabinet to the UPS
3. Connect the RS232 cable from the Battery Cabinet 1 RS232 to UPS/BC port to the UPS RS232C port.
(Figure 3)
4. Connect Battery Cabinet 1 CN12A to UPS CN12,
5. Connect Battery Cabinet 1 CN13A to UPS CN13,
6. Connect Battery Cabinet 1 CN14A to UPS CN14.
If a second battery cabinet is to be installed go to step 7, otherwise go to Section 4.3.
7. Connect the RS232 cable from the Battery Cabinet 2 RS232 to UPS/BC port to the Battery Cabinet 1
RS232 to BC port. (Figure 3)
8. Connect Battery Cabinet 2 CN12A to cabinet 1 CN22,
9. Connect Battery Cabinet 2 CN13A to cabinet 1 CN23,
10. Connect Battery Cabinet 2 CN14A to cabinet 1 CN24.
10
1600XPi 8/10 kVA UPS

Figure 5 Cabling 8/10kVA UPS to Battery Cabinet

1600XPi Series Battery Cabinet Installation and Operation Manual 64024-006
CN22 CN23 CN24
BC-1825 BATTERY CABINET