Dimensions - Ycas1065 - Ycas1215 (Si); Fig. 53 - Model Ycas1065 - Ycas1215 (Si) - York YCAS Series Installation Operation & Maintenance

Air-cooled screw liquid chillers
Hide thumbs Also See for YCAS Series:
Table of Contents

Advertisement

Technical Data
DIMENSIONS – YCAS1065 - YCAS1215 (SI)
All dimensions are in
mm un less oth er wise
noted.
CONTROL ENTRY
(12) 13
CONDUIT K.O.'S
229
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, re li able
operation and ease of maintenance. Site re stric tions may compromise min i mum clearances indicated below, resulting in un pre dict able air ß ow
pat terns and possible di min ished performance. YORK's unit controls will optimize operation without nui sance high pres sure safety cutout;
however, the system designer must con sid er potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; con trol panel end to wall - 1.2m; top
- no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.
FIG. 53 – MODEL YCAS1065 - YCAS1215 (SI)
100
711
51
120
51 TYP.
VIEW B-B
B
CONTROL
TRANSFORMER
SERVICE SWITCH
48
2235
2331
VIEW A-A
178
CONTROL
OPENING
(229 HIGH)
51
305
POWER
OPENING
(533 HIGH)
VIEW C-C
MICROCOMPUTER
CONTROL CENTER
B
OPTIONS PANEL
C
540
C
78 (EDGE OF
BASE TO COOLER
CONNECTION)
FORM 201.19-NM8 (804)
1067
800
191
LD06107