Dimensions - Ycas0965 (Si); Fig. 52 - Model Ycas0965 Dimensions (Si) - York YCAS Series Installation Operation & Maintenance

Air-cooled screw liquid chillers
Hide thumbs Also See for YCAS Series:
Table of Contents

Advertisement

Technical Data
All dimensions are in mm
un less oth er wise noted.
CONTROL ENTRY
(12) 13
CONDUIT K.O.'S
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, re li able
operation and ease of maintenance. Site re stric tions may compromise min i mum clearances indicated below, resulting in un pre dict able air ß ow
pat terns and possible di min ished performance. YORK's unit controls will optimize operation without nui sance high pres sure safety cutout;
however, the system designer must con sid er potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; con trol panel end to wall - 1.2m; top
- no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.
FIG. 52 – MODEL YCAS0965 DIMENSIONS (SI)
98
DIMENSIONS – YCAS0965 (SI)
711
51 TYP.
229
VIEW B-B
48
VIEW A-A
178
CONTROL
OPENING
(229 HIGH)
51
51
305
120
POWER
OPENING
(533 HIGH)
VIEW C-C
MICROCOMPUTER
CONTROL CENTER
B
OPTIONS PANEL
B
C
540
CONTROL
C
TRANSFORMER
SERVICE SWITCH
78 (EDGE OF
BASE TO COOLER
CONNECTION)
2235
2331
FORM 201.19-NM8 (804)
1067
800
191
LD05586
LD06107
YORK INTERNATIONAL