MODEL
LEAVING WATER
TEMPERATURE (°C)
NUMBER
YCAS
MIN.
5.0
0685
5.0
0775
5.0
0835
5.0
0905
5.0
0965
5.0
1065
5.0
1135
5.0
1215
NOTES:
1. For leaving brine temperature below 5 °C, contact your nearest YORK ofÞ ce for application requirements.
2. For leaving water temperature higher than 13°C, contact the nearest YORK ofÞ ce for application guidelines.
3. The evaporator is protected against freeze-up to -28.8°C with an electrical heater as standard.
Excessive fl ow, above the max GPM,
will damage the evaporator.
YORK INTERNATIONAL
TEMPERATURE AND FLOWS
(SI Units)
1
MAX.
2
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
EVAPORATOR FLOW
(L/S)
3
MIN.
MAX.
18.5
67.6
21.0
76.0
21.0
76.0
21.0
76.0
21.0
76.0
27.2
101.0
27.2
101.0
27.2
101.0
FORM 201.19-NM8 (804)
AIR ON
CONDENSER (°C)
MIN.
MAX
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
47
7