Table 3 - Default Values Table - York YCAS Series Installation Operation & Maintenance

Air-cooled screw liquid chillers
Hide thumbs Also See for YCAS Series:
Table of Contents

Advertisement

The default values shown below are entered into
memory, when the program option is selected. The
list also provides the low and high limits the micro
will accept.
TABLE 3 – DEFAULT VALUES TABLE (MINIMUM/MAXIMUM)
Program Value
Display Language
Discharge Pressure Cutout
Discharge Pressure Unload
Suction Pressure Cutout
High Ambient Air Temp Cutout
Low Ambient Ait Temperature Cutout
Leaving Chilled Liquid Temp Cutout
High Motor Current Unload
Anti Recycle Time
Local / Remote Mode
Units Mode
Lead / Lag Control Mode
Power Failure Restart Mode
Motor Current Averaging Cutout
Suction Superheat Setpoint
YORK INTERNATIONAL
Mode
Low Limit
--
NA
200 PSIG
--
13.8 Bars
200 PSIG
--
13.8 Bars
44.0 PSIG
Water Cooling
3.03 Bars
5.0 PSIG
Glycol Cooling
0.34 Bars
100.0 ºF
--
37.8 ºC
Standard
Ambient
Low
0 ºF
Ambient
-17.8 ºC
Water Cooling
8.0 ºF
Glycol Cooling
-13.3 ºC
Low Temp Glycol
-5.0 ºF
-20.5 ºC
--
30%
--
300 sec
--
NA
--
NA
--
NA
--
NA
--
30% FLA
9.0 ºF
EEV
5.0 ºC
FORM 201.19-NM8 (804)
High Limit
Default
NA
English
399 PSIG
399 PSIG
27.5 Bars
27.5 Bars
399 PSIG
375 PSIG
27.5 Bars
25.9 Bars
70.0 PSIG
44.0 PSIG
4.83 Bars
30.3 Bars
70.0 PSIG
44.0 PSIG
4.83 Bars
3.03 Bars
130.0 ºF
130.0 ºF
54.4 ºC
54.4 ºC
--
--
25.0 ºF
--
--
-3.9
50.0 ºF
25.0 ºF
10.0 ºC
-3.9 ºC
--
--
36.0
--
--
2.2
36.0 ºF
36.0 ºF
2.2 ºC
2.2 ºC
36.0 ºF
36.0 ºF
2.2 ºC
2.2 ºC
105%
100
600 sec
600 sec
NA
Local
NA
Imperial
NA
Automatic
NA
Automatic
110% FLa
70 % FLA
15.0 ºF
12.0 ºF
8.3 ºC
6.6 ºC
8
183