Emerson Rosemount 5408 Reference Manual page 89

Level transmitters, non-contacting radar with hart protocol
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Reference Manual
00809-0100-4408
Figure 5-1: Calibration Offset
A. Positive Calibration Offset value
B. Negative Calibration Offset value
C. Reported level
D. Actual level
5.7.1
Run verify level using Rosemount Radar Master Plus
Verify and adjust level measurement by comparing it to a hand-gauged measurement.
Prerequisites
Note
Before running Verify Level, make sure that: the product surface is calm, the tank is not
being filled or emptied, and the actual level is well above the tank bottom.
Procedure
1. Under Configure, select Verify Level to check your level measurement.
2. Follow the on-screen instructions.
5.7.2
Run verify level using AMS Device Manager and
handheld communicator
Verify and adjust level measurement by comparing it to a hand-gauged measurement.
Prerequisites
Note
Before running Verify Level, make sure that: the product surface is calm, the tank is not
being filled or emptied, and the actual level is well above the tank bottom.
Rosemount 5408 and 5408:SIS Level Transmitters
Verify Level is also available via the Guided Setup wizard
Configuration
February 2020
89