Markings
Safety parameter
Voltage U
Current I
Power P
Capacitance C
Inductance L
Specific Conditions of Use (X):
1. The Model 5408 Level Transmitter will not pass the 500Vrms dielectric strength test
2. Plastic wire-on tag, Plastic part of Process Seal Antenna and Non-standard paint
3. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C
4. The Transmitter can be installed in the boundary wall between EPL Ga and EPL Gb
5. Using the box provided on the nameplate, the User shall permanently mark the
6. The applicable temperature class, ambient temperature range and process
Rosemount 5408 and 5408:SIS Level Transmitters
II 1G Ex ia IIC T4...T2 Ga
II 1/2G Ex ib IIC T4...T2 Ga/Gb
II 1D Ex ia IIIC T85°C...T250°C Da
-60 °C ≤ Ta ≤ +70 °C
i
i
i
i
i
between the circuits and the earth ground. This must be taken into account during
installation.
options (paint options other than Rosemount Blue) may cause risk from
Electrostatic discharge. Avoid installation that could cause electrostatic build-up,
and only clean with a damp cloth.
greater than the maximum specified ambient temperature for location where
installed.
location. In this configuration, the process connection is EPL Ga, while the
transmitter housing is EPL Gb. Refer to Control Drawing D7000002-885.
type of protection chosen for the specific installation. Once the type of protection
has been marked it shall not be changed.
temperature range of the equipment is as follows:
Product certifications
®
HART
30 V
133 mA
1.0 W
7.3 nF
0
February 2020
223