Table 3-7: Nozzle Requirements for Parabolic Antenna, in Inches (Millimeters)
Nozzle size (D)
Pipe schedule std, Ø 8 in. (200
mm)
Pipe schedule std, Ø10 in. (250
mm)
(1)
Note that the inside of the nozzle must be smooth (i.e. avoid bad welding, rust, or deposit).
3.3.8
Still pipe/chamber installations
Installation in still pipe/chamber is recommended for tanks where there are excessive
foaming or turbulence. Still pipe/chamber may also be used to avoid disturbing objects in
the tank.
For more information and installation requirements, refer to the Best Practices for Using
Radar in Still Pipes and Chambers
Still pipe
Consider the following still pipe requirements:
Pipe
Holes
Rosemount 5408 and 5408:SIS Level Transmitters
Inclination angle (α)
12°
15°
12°
15°
Technical
Pipes should be an all-metal material.
Pipe should have a constant inside diameter.
The inner surface must be smooth and clear of any rough edges. (Smooth
pipe joints are acceptable, but may reduce accuracy.)
The end of the pipe must extend beyond the zero level.
Maximum hole diameter is 1 in. (25 mm).
Minimum distance between holes is 6 in. (150 mm).
Holes should be drilled on one side only and deburred.
Drill one hole above maximum product surface.
Mechanical installation
Maximum nozzle height
(1)
(H)
6.1 (155)
3.4 (85)
1.6 (40)
1.2 (30)
1.0 (25)
0.6 (15)
17.2 (440)
10.2 (260)
7.1 (180)
5.1 (130)
3.9 (100)
3.0 (75)
Note.
February 2020
29