Service and troubleshooting
February 2020
Follow all plant safety rules and procedures.
In Explosion Proof/Flameproof and Non-Incendive/Type n installations, do not remove
the transmitter covers when power is applied to the unit.
Do not remove the process connection while in operation. Removing while in
operation may cause process gas leaks.
Cleaning
To avoid electrostatic charges, use only a damp cloth to clean the PTFE surfaces. Clean the
PTFE sealing with care.
The transmitter is suitable for:
Cleaning-Out-of-Place (COP)
Cleaning-In-Place (CIP) up to 160 °F (71 °C)
Steaming-In-Place (SIP) up to 275 °F (135 °C)
7.7.1
Flanged version
Disassembly procedures
Procedure
1. Insert two flathead screwdrivers between the PFTE sealing and flange.
2. Gently push the screwdriver handles forward until the PTFE sealing pops out.
142
Reference Manual
00809-0100-4408