Siemens SIRIUS 3RW5 Equipment Manual page 86

Soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW5:
Table of Contents

Advertisement

Configuring
6.3 Configuring the 3RW5 Soft Starter
6.3.2.6
Silent interval time
Setting options
● 3RW5 HMI High Feature
Menu: "Parameter > Communication module > Modbus RTU > Silent interval time"
You will find more information on operating the 3RW5 HMI High Feature in the
Equipment Manual of the 3RW5 soft starter.
● User program via the "Modbus RTU communication parameters" data table (Page 177)
Parameters
Parameter
Silent interval time
86
Description
The silent interval time is the interval between 2 Modbus telegrams.
For the setting "Automatic" (factory setting), the minimum silent
interval time of the baud rate used is automatically set. For example,
2 ms for the baud rate 19.2 kbit/s. You will find the setting range of the
silent interval time in chapter Modbus RTU communication parameters
(Page 177).
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
SIRIUS 3RW5 Modbus communication module