Siemens SIRIUS 3RW5 Equipment Manual page 160

Soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW5:
Table of Contents

Advertisement

Appendix
A.2 Data tables
A.2.16
Statistic data
Only read access (r) to the statistical data is possible via Function Codes 03 and 04.
Register
Byte
Data format
Address
high /
low
0x8C01
high
Unsigned8
[35841]
0x8C02
high
Unsigned16
[35842]
0x8C03
high
Unsigned32
[35843]
0x8C05
high
Unsigned32
[35845]
0x8C07
high
Unsigned32
[35847]
0x8C09
high
Unsigned16
[35849]
0x8C0B
high
Signed32
[35851]
0x8C0D
high
Signed32
[35853]
0x8C0F
high
Unsigned32
[35855]
0x8C11
high
Unsigned32
[35857]
0x8C13
high
Unsigned32
[35859]
0x8C15
high
Unsigned32
[35861]
0x8C17
high
Unsigned32
[35863]
0x8C1A
high
Unsigned16
[35866]
0x8C1B
high
Unsigned16
[35867]
0x8C1F
high
Unsigned32
[35871]
0x8C21
high
Unsigned32
[35873]
0x8C23
high
Unsigned32
[35875]
0x8C25
high
Unsigned32
[35877]
0x8C27
high
Unsigned32
[35879]
0x8C3B
high
Float32
[35899]
160
Statistic data
Phase current max (%)
Last tripping current IA (%)
Operating hours - device
Number of starts motor CW
Number of starts motor CCW
Number of motor overload trips
Phase current max (rms)
Last tripping current IA (rms)
Operating hours - motor
Operating hours - motor current =
18 ... 49.9% x Iemax
Operating hours - motor current =
50 ... 89.9% x Iemax
Operating hours - motor current =
90...119.9 (% x Iemax)
Operating hours - motor current =
120...1000 (% x Iemax)
Number of switching element
overload trips
Number of bypass overload trips
Number of braking stops
Number of starts output1
Number of starts output2
Number of starts output3
Number of starts output4
Active energy import (total)
Range of values
0 ... 796.9 %
0 ... 1 000 %
0 ... 4 294 967 295 s
0 ... 4 294 967 295
0 ... 4 294 967 295
0 ... 65 535
-20 000 ... 20 000 A
-20 000 ... 20 000 A
0 ... 4 294 967 295 s
0 ... 4 294 967 295 s
0 ... 4 294 967 295 s
0 ... 4 294 967 295 s
0 ... 4 294 967 295 s
0 ... 65 535
0 ... 65 535
0 ... 4 294 967 295
0 ... 4 294 967 295
0 ... 4 294 967 295
0 ... 4 294 967 295
0 ... 4 294 967 295
0 ...
4 294 967 295 Wh
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
In steps
3RW
of
50 /
55 /
52
55-F
1)
2)
3.125 %
r
r
3.125 %
r
r
1 s
r
r
1
r
r
1
-
r
1
r
r
0.01 A
r
r
0.01 A
r
r
1 s
r
r
1 s
r
r
1 s
r
r
1 s
r
r
1 s
r
r
1
r
r
1
r
r
1
-
r
1
-
r
1
-
r
1
-
r
1
-
r
1 Wh
-
r

Advertisement

Table of Contents
loading

Table of Contents