A.2.20
Modbus RTU communication parameters
Read access (r) to the communication parameters is possible via Function Codes 03 and 04.
Write access (w) is possible for individual communication parameters via Function Codes 06
and 16.
Register
Byte
Data format
Address
high /
low
0xA202
high
Unsigned32
[41474]
0xA204
high
Unsigned16
[41476]
0xA206
high
Unsigned8
[41478]
low
Unsigned8
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Parameter
Range of values
[encoding]
Access monitoring
[5 000 ... 10 000]
time
[5 000] 5 s
[10 000] 10 s
Silent interval time
Increment: 0.1 ms
Baud rate: 1.2 kbit/s
32 ... 6 553.5 ms
[320 ... 65 535]
Baud rate: 2.4 kbit/s
16 ... 6 553.5 ms
[160 ... 65 535]
Baud rate: 4.8 kbit/s
8 ... 6 553.5 ms
[80 ... 65 535]
Baud rate: 9.6 kbit/s
4 ... 6 553.5 ms
[40 ... 65 535]
Baud rate: 19.2 kbit/s
2 ... 6 553.5 ms
[20 ... 65 535]
Baud rate: 38.4 kbit/s
1 ... 6 553.5 ms
[10 ... 65 535]
Baud rate: 57.6 kbit/s
0.7 ... 6 553.5 ms
[7 ... 65 535]
Baud rate: 76.8 kbit/s
0.5 ... 6 553.5 ms
[5 ... 65 535]
Baud rate: 115.2 kbit/s 0.3 ... 6 553.5 ms
[3 ... 65 535]
Automatic
[0]
Baud rate
[0 ... 12]
[0] Automatic
[1] 115.2 kbit/s
[4] 76.8 kbit/s
[6] 57.6 kbit/s
[7] 38.4 kbit/s
[8] 19.2 kbit/s
[9] 9.6 kbit/s
[10] 4.8 kbit/s
[11] 2.4 kbit/s
[12] 1.2 kbit/s
Port configuration
[0 ... 4]
[0] Automatic
[1] 1 start, 8 data, 1 stop bit, even parity
[2] 1 start, 8 data, 1 stop bit, odd parity
[3] 1 start, 8 data, 2 stop bit, no parity
[4] 1 start, 8 data, 1 stop bit, no parity
1)
Appendix
A.2 Data tables
Default
Access
5 000
r/w
0
r/w
1)
8
r/w
1
r/w
177