Response telegram
Modbus TCP:
Address Field
7 bytes
-
Modbus RTU:
Slave address
1 byte
-
Example
Setting the bit addresses of the "Motor CW" and "Creep speed" commands to a logical one
and reading the process image input:
● Address Field or slave address: The address of the 3RW5 soft starter is not entered in
the example (-).
● The CRC CHECK is not entered in the example (-).
● The commands start in register address 0x8200. The bit addresses of the commands are:
– "Motor CW": 0x8200
– "Creep speed": 0x8206
● The remaining bits of the byte are controlled with a logical zero (0x41).
● The process image input starts at register address 0x8000 and occupies 8 registers.
● As feedback, the process image input is returned. In the example, the returned data are
not entered (-). Note that the requested commands are not returned as a new status in
the exact same cycle because implementation of the commands takes a while. The new
status is not returned in the process image input until several communication cycles later.
You will find the data tables for the process image output and process image input in
chapters Process image output (PIQ) (Page 150) and Process image input (PII) (Page 148).
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Function Code
1 byte
0x17
Function Code
Number of bytes N Data
1 byte
1 byte
0x17
0x0010
Messages and diagnostics
Number of bytes N
1 byte
0x0010
N x 2 bytes
-
7.2 Function Codes
Data
N x 2 bytes
-
CRC
2 bytes
-
111