Siemens SIRIUS 3RW5 Equipment Manual page 76

Soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW5:
Table of Contents

Advertisement

Configuring
6.3 Configuring the 3RW5 Soft Starter
1. Set the IP parameters in the 3RW5 communication module.
The following procedures are possible:
– Via SIRIUS Soft Starter ES (TIA Portal) over the local interface on the
– Via the 3RW5 HMI High Feature
Note the information in chapter IP parameters (Page 77).
2. Start the Modbus TCP client in your automation system and address the server
(3RW5 soft starter) using the previously set IP parameters.
When using a SIMATIC S7-1500, for example, integrate the FB "MB_CLIENT" into the
user program.
Note the information in chapter IP parameters (Page 77).
3. Load the configuration into the client (if necessary).
Result
The 3RW5 soft starter is configured in the Modbus TCP system and can communicate with
other Modbus TCP devices via the 3RW5 Modbus TCP communication module.
76
3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created
Soft Starter > "Device configuration" > Window "Work area" > Communication module
"Modbus TCP" > Inspector window "Modbus TCP" > Tab "Properties" > Tab
"General" > "Interface"
Further information on the operation of SIRIUS Soft Starter ES (TIA Portal) can be
found in the online help of SIRIUS Soft Starter ES (TIA Portal).
Menu: "Parameter > Communication module > Modbus TCP > IP address"
Menu: "Parameter > Communication module > Modbus TCP > Subnet mask"
Menu: "Parameter > Communication module > Modbus TCP > Router address"
You will find more information on operating the 3RW5 HMI High Feature in the
Equipment Manual of the 3RW5 soft starter.
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003