Siemens SIRIUS 3RW5 Equipment Manual page 79

Soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW5:
Table of Contents

Advertisement

Procedure
...
1. Start the Modbus RTU master in your automation system and address the slave
(3RW5 soft starter) using the station address currently stored in the 3RW5 Modbus RTU
communication module. For first commissioning and after restoration of the factory
settings, this station address has the factory setting (Page 82).
2. By means of the "Modbus RTU communication parameters" (Page 177) data table, set
the required station address in the 3RW5 soft starter.
Note the information in chapter Station address (Page 82).
Note
Writing down the station address
Write down the set station address that you have just set. To change the configuration,
the station address currently stored in the 3RW5 Modbus RTU communication module
must be known. You need a 3RW5 HMI High Feature to restore the factory settings.
3. Enter the modified station address of the slave in the Modbus RTU master.
Note the information in chapter Station address (Page 82).
4. Load the configuration into the Modbus RTU master (if necessary).
Result
The 3RW5 soft starter is configured in the Modbus RTU system and can communicate with
other Modbus RTU devices via the 3RW5 Modbus RTU communication module.
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Programmable logic controller / Modbus RTU master, e.g. SIMATIC S7-1500
PC or programming device with configuration software of controller
Modbus RTU
SIRIUS 3RW5 soft starter / slave
: Steps to be taken in the procedure
6.3 Configuring the 3RW5 Soft Starter
Configuring
79