Supported Exception Codes - Siemens SIRIUS 3RW5 Equipment Manual

Soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW5:
Table of Contents

Advertisement

7.3.2

Supported Exception Codes

Exception Code
Meaning in
accordance
with Modbus
specification
1 (= 0x01)
Illegal function
2 (= 0x02)
Illegal data
address
3 (= 0x03)
Illegal data
value
4 (= 0x04)
Failure in
associated
device
6 (= 0x06)
Busy, rejected
message
Note
TIA Portal
Note that the TIA portal does not support all Exception Codes. Unsupported Exception
Codes are detected and evaluated as Exception Code 0x03. You will find further information
in the online help for the TIA Portal.
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Cause
Brief description
Impermissible
The requested Function Code is
Function Code
not supported. Pay particular
attention to chapter Function
Codes (Page 98).
Impermissible bit
Address does not exist. For
and register
functions that work with an
address in the
addressing range, all addresses
Modbus TCP
affected by the request are
server or
checked.
Modbus RTU
slave
Impermissible
The number of addresses is not
data value in the
correct. The number of
Modbus TCP
parameters for the requested
server or
function was too high (or 0)
Modbus RTU
slave
Internal error in
There is an unspecified error in
the Modbus TCP
the Modbus TCP server or
server or
Modbus RTU slave that
Modbus RTU
prevented execution of the
slave
request.
Modbus TCP
The device is busy and unable
server or
to process the request at this
Modbus RTU
time.
slave is not ready
to receive
Messages and diagnostics
7.3 Exception Codes
Example
The Function Code 43 was
requested. The 3RW5 Modbus
communication modules do not
support the Function Code 43.
Request for reading the register
with address 0x7000. The
register address 0x7000 is not
defined for 3RW5 Modbus
communication modules.
Request for writing the register
with address 0xA102 with the
value 7 000. The parameter
"Access monitoring time" can
only have the value 5 000
or 10 000.
Error in the 3RW5 soft starter so
that the 3RW5 soft starter
cannot answer the request.
This can occur following a
parameterization operation via
Modbus when the new
parameter values are
transferred to the device.
113